OmniStax Series
The OmniStax series of 29.9kW/30kW/40kW/50/60kW hybrid inverters integrates charging and discharging, grid-tied photovol- taic systems, grid-tied/off-grid switching, off-grid backup power, generator charging, and EMS/APP functionalities. lt is dedicated to delivering safe, intelligent, simplified, and efficient energy solutions for microgrids and small-to-medium commercial scenarios.
-
Highly Integrated
200% PV Over-Sizing,Capable of fast charging at up to 160A,Seamless grid to off-grid transition <10ms,Gen Charge and EMS/APP.
Al-Powered Arc Fault Detection
Supports Multiple Operation modes, lncluding Self-Con- sumption, Peak Shaving, Battery Backup, Designed for applications such as Microgrids and Zero-Carbon Campuses etc.
-
High Reliability
SiC Platform, The Max Dis/Chg Efficiency is 97.8%. The Max system Efficiency is 98.6%.
lngress Protection :lP66 Designed for harsh outdoor operation
Warranty: 5-Year standard 10-Year optional
-
Highly Compatible
Supports up to 21A Solar Panels.
Compatible with 100-314Ah Battery Cell. Flexible configuration with phased investment.
-
Remote Monitoring and Maintenance
Supports 100Mbps Network, Remote Seamless Upgrade, and Online Operation and Mainte- nance
| Technical Data | ES-29.9K-TP ES-29.9K-TP/C |
ES-30K-TP ES-30K-TP/C |
ES-40K-TP ES-40K-TP/C |
ES-50K-TP ES-50K-TP/C |
ES-60K-TP ES-60K-TP/C |
|---|---|---|---|---|---|
| PV Input | |||||
| Max Usable PV Input Power | 59.8kW | 60kW | 80kW | 100kW | 100kW |
| Max Input Voltage | 1000V | ||||
| Rated Voltage | 620V | ||||
| Start-up Voltage | 150V | ||||
| MPPT Voltage Range | 150V-850V | ||||
| Max Input Current | 42A/42A/42A | 42A/42A/42A/42A | |||
| Max Short Circuit Current | 55A/55A/55A | 55A/55A/55A/55A | |||
| Number of MPPT Channel | 3 | 4 | |||
| Number of Strings per MPPT Channel | 2 | ||||
| Battery Input/Output | |||||
| Battery Type | Li-ion | ||||
| Number of Battery Input | 2 | ||||
| Max Charge Power | 29.9kW | 30kW | 40kW | 50kW | 60kW |
| Max Discharge Power | 29.9kW | 30kW | 40kW | 50kW | 60kW |
| Battery Voltage range | 150V-900V | ||||
| Max Charge Current | 80A/80A(Supports paralleling) | ||||
| Max Discharge Current | 80A/80A(Supports paralleling) | ||||
| Grid side | |||||
| Rated Output Power | 29.9kW | 30kW | 40kW | 50kW | 60kW |
| Rated Output Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA | 60kVA |
| Rated Output Current | 43.3A | 43.5A | 58.0A | 72.5A | 87A |
| Rated Input Apparent Power | 59.8kVA | 60kVA | 80kVA | 100kVA | |
| Rated Input Current | 86.7A | 87.0A | 115.9A | 144.9A | |
| Rated Voltage | 3L+N+PE, 230V/400V | ||||
| Rated Frequency | 50Hz | ||||
| Output Power Factor | 0.8 leading - 0.8 lagging | ||||
| THDi | <3% | ||||
| Generator | |||||
| Max Input Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA | 60kVA |
| Rated Current | 43.3A | 43.5A | 58.0A | 72.5A | 87A |
| Rated Voltage | 3L+N+PE, 230V/400V | ||||
| Rated Frequency | 50Hz | ||||
| Output AC(Back-up) | |||||
| Rated Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA | 60kVA |
| Rated Output Current | 43.3A | 43.5A | 58.0A | 72.5A | 87A |
| Rated Voltage | 3L+N+PE, 230V/400V | ||||
| Rated Frequency | 50Hz | ||||
| Maxbalance Power per Phase | 10.0kVA | 10.0kVA | 13.3kVA | 16.7kVA | 20kVA |
| Back-up Switch Time | 10ms | ||||
| THDv(@Linear Load) | <2% | ||||
| Overload | 1.5 times of rated power, 10s | 1.25 times of rated power, 10s | |||
| Efficiency | |||||
| Max Efficiency | 98.60% | ||||
| BAT Charged by PV Max Efficiency | 98.50% | ||||
| Max Battery to AC Efficiency | 97.70% | ||||
| MPPT Efficiency | 99.90% | ||||
| Protection | |||||
| Anti-islanding protection | Yes | ||||
| Insulation Resistor detection | Yes | ||||
| Output over current protection | Yes | ||||
| Output short protection | Yes | ||||
| Output over voltage protection | Yes | ||||
| DC reverse polarity protection | Yes | ||||
| DC Surge Protection/AC Surge Protection | Type II /Type III | ||||
| Integrated AFCI | Yes | ||||
| General data | |||||
| Dimensions(W/H/D) | 830mm×635mm×300mm | ||||
| Weight | <89kg | ||||
| Operation temperature range | -30℃~+60℃ (Derate above 45℃) | ||||
| Topology | Non-Isolated | ||||
| Relative humidity | 0-95% | ||||
| Ingress protection | IP66 | ||||
| Noise emission | <65 dB(A) | ||||
| Cooling concept | Intelligent redundant fan-cooling | ||||
| Maxoperation altitude | 3000m | ||||
| Display | LED/LCD+APP | ||||
| Communication | CAN, RS485, Ethernet | ||||
| Warranty | 5 years | ||||
| Certification | |||||
| Grid connection standard | EN 50549-1/EN 50549-10,NRS 097-2-1,AS4777.2 | ||||
| Safty/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4 | ||||
| Note | Same model. Suffix /C indicates the unit is fitted with an LCD display, all other parameters remain identical. | ||||