OmniStax Series
The OmniStax series of 29.9kW/30kW/40kW/50kW hybrid inverters integrates ocharging and discharging, grid-tied photovoltaic systems, grid-tied/off-grid switching, off-grid backup power, geneerator charging, and EMS/APP functionalities. It is dedicated to delivering safe, intelligent, simplified, and efficient energy solutions for microgrids and small-to-medium commercial scenarios.
-
HIGHLY INTEGRATED
200% PV Over-Sizing, Capable of fast charging at up to 160A, Seamless grid to off-grid transition <10ms, Gen Charge and EMS/APP.
AI-Powered Arc Fault Detection
Supports Multiple Operation modes, Including Self-Consumption, Peak Shaving, Battery Backup, Designed for applications such as Microgrids and Zero-Carbon Campuses etc.
-
HIGH RELIABILITY
SiC Platform, The Max system Efficiency is 98.6%.
Ingress Protection :IP66 Designed for harsh outdoor operation
Warranty: 5-Year standard 10-Year optional
-
HIGHLY COMPATIBLE
Supports up to 21A Solar Panels.
Compatible with 100-314Ah Battery Cell.Flexible configuration with phased investment.
-
REMOTE MONITORING AND MAINTENANCE
Supports 100Mbps Network,Remote Seamless Upgrade,and Online Operation and Maintenance
| Technical Data | ES-29.9K-TP | ES-30K-TP | ES-40K-TP | ES-50K-TP |
|---|---|---|---|---|
| PV Input | ||||
| Max Usable PV Input Power | 59.8kW | 60kW | 80kW | 100kW |
| Max Input Voltage | 1000V | |||
| Rated Voltage | 625V | |||
| Start-up Voltage | 150V | |||
| MPPT Voltage Range | 150V-850V | |||
| Max Input Current | 42A/42A/42A | 42A/42A/42A | ||
| Max Short Circuit Current | 55A/55A/55A | 55A/55A/55A | ||
| Number of MPPT Channel | 3 | 4 | ||
| Number of Strings per MPPT Channel | 2 | 2 | ||
| Battery Input/Output | ||||
| Battery Type | Li-ion | |||
| Number of Battery Input | 2 | |||
| Max Charge Power | 29.9kW | 30kW | 40kW | 50kW |
| Max Discharge Power | 29.9kW | 30kW | 40kW | 50kW |
| Battery Voltage range | 150V-810V | |||
| Max Charge Current | 80A/80A(Supports paralleling) | |||
| Max Discharge Current | 80A/80A(Supports paralleling) | |||
| Grid side | ||||
| Rated Output Power | 29.9kW | 30kW | 40kW | 50kW |
| Rated Output Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA |
| Rated Output Current | 43.3A | 43.5A | 58.0A | 72.5A |
| Rated Input Apparent Power | 59.8kVA | 60kVA | 80kVA | 100kVA |
| Rated Input Current | 86.7A | 87.0A | 115.9A | 144.9A |
| Rated Voltage | 3L+N+PE, 230V/400V | |||
| Rated Frequency | 50Hz | |||
| Output Power Factor | 0.8 leading - 0.8 lagging | |||
| THDi | <3% | |||
| Generator | ||||
| Max Input Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA |
| Rated Current | 43.3A | 43.5A | 58.0A | 72.5A |
| Rated Voltage | 3L+N+PE, 230V/400V | |||
| Rated Frequency | 50Hz | |||
| Output(Back-up) | ||||
| Rated Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA |
| Rated Output Current | 43.3A | 43.5A | 58.0A | 72.5A |
| Rated Voltage | 3L+N+PE, 230V/400V | |||
| Rated Frequency | 50Hz | |||
| Maxbalance Power per Phase | 10.0kVA | 10.0kVA | 13.3kVA | 16.7kVA |
| Back-up Switch Time | 10ms | |||
| THDv(@Linear Load) | <2% | |||
| Overload | 1.5 times of rated power, 10s | |||
| Efficiency | ||||
| Max Efficiency | 98.60% | |||
| BAT Charged by PV Max Efficiency | 98.50% | |||
| Max Battery to AC Efficiency | 97.70% | |||
| MPPT Efficiency | 99.90% | |||
| Protection | ||||
| Anti-islanding protection | Yes | |||
| Insulation Resistor detection | Yes | |||
| Output over current protection | Yes | |||
| Output short protection | Yes | |||
| Output over voltage protection | Yes | |||
| DC reverse polarity protection | Yes | |||
| DC Surge Protection/AC Surge Protection | Type II /Type III | |||
| Integrated AFCI | Yes | |||
| General data | ||||
| Dimensions(W/H/D) | 830mm×635mm×300mm | |||
| Weight | <85kg | |||
| Operation temperature range | -30℃~+60℃ (Derate above 45℃) | |||
| Topology | Non-Isolated | |||
| Relative humidity | 0-95% | |||
| Ingress protection | IP66 | |||
| Noise emission | <65 dB(A) | |||
| Cooling concept | Intelligent redundant fan-cooling | |||
| Maxoperation altitude | 3000m | |||
| Display | LED/LCD+APP | |||
| Communication | CAN, RS485, Ethernet | |||
| Warranty | 5 years | |||
| Certification | ||||
| Grid connection standard | EN 50549-1/EN 50549-10,NRS 097-2-1,AS4777.2 | |||
| Safty/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4 | |||